The Air Handling Unit (AHU) is the central component of any ducted HVAC system. It conditions outside and recirculated air — cooling, dehumidifying, filtering, and distributing it through the building ductwork. Selecting the right AHU requires calculating four key parameters: supply airflow, cooling coil capacity, chilled water flow rate, and fan power. This guide walks you through each step with worked examples.
AHU Components — What You Are Sizing
A typical chilled water AHU consists of:
- Filter section: G4 pre-filter + F7 bag filter (for commercial); HEPA for healthcare
- Cooling coil: Chilled water or DX coil to cool and dehumidify air
- Heating coil: LPHW or electric for winter or reheating
- Supply fan: Centrifugal or axial fan to overcome duct system resistance
- Fresh air damper + return air damper: To mix outdoor and recirculated air
- Drain pan: To collect condensate from the cooling coil
Step 1 — Calculate Supply Airflow
Supply airflow is determined from the sensible cooling load and the supply air temperature:
Minimum Ventilation Airflow Check
Always verify the calculated airflow meets minimum ventilation requirements per NBC/ASHRAE 62.1:
- Office spaces: minimum 10 L/s per person
- Retail: 10 L/s per person + 3 L/s·m² area
- Meeting rooms: 10 L/s per person
The supply airflow must satisfy both the cooling load requirement and the minimum ventilation requirement — whichever is larger governs.
Step 2 — Size the Cooling Coil
Coil Entering and Leaving Conditions
Coil Face Area
Step 3 — Chilled Water Flow Rate
Use our AHU Sizing Calculator to compute supply airflow, coil capacity, chilled water flow rate, and fan power in one step. Also check the HVAC Heat Load Calculator to first determine your building cooling load.
Step 4 — Fan Sizing (Static Pressure and Power)
Total External Static Pressure
The AHU fan must overcome the resistance of the entire duct system — supply ductwork, fittings, diffusers, return ductwork, and filters. Typical values for commercial buildings:
| System Component | Typical Pressure Drop |
|---|---|
| G4 pre-filter (clean) | 50–80 Pa |
| F7 bag filter (clean) | 80–120 Pa |
| Cooling coil (4-row) | 100–150 Pa |
| Supply ductwork (main) | 80–150 Pa |
| Diffuser and terminal | 20–50 Pa |
| Return ductwork | 50–100 Pa |
| Typical Total ESP | 350–650 Pa |
Worked Example — Full AHU Sizing
AHU vs FCU — When to Use Which
| Parameter | AHU | FCU |
|---|---|---|
| Typical capacity | 10–200+ kW | 0.5–10 kW |
| Fresh air handling | Yes — central OA treatment | Limited (via separate DOAS) |
| Filtration | High efficiency (F7, HEPA) | Basic G4 only |
| Zone control | Complex (VAV boxes needed) | Simple (on/off or 3-speed) |
| Best for | Large open offices, malls, hospitals | Hotel rooms, small offices |
Common AHU Sizing Mistakes
- Sizing only for sensible load and ignoring latent: The cooling coil must handle total heat (sensible + latent). Using only sensible load for coil selection results in an undersized coil that cannot dehumidify adequately in Indian humidity conditions.
- Using too high a face velocity: Face velocities above 2.5 m/s cause moisture carryover — condensate droplets are blown into the ductwork, causing wet insulation and mould growth downstream.
- Not sizing for dirty filter pressure drop: Fan ESP must be calculated at dirty filter conditions. Clean filter pressure drop × 2 is often used for the dirty condition to size the fan correctly.
- Ignoring duct system balance: If the AHU serves multiple zones with different pressure drops, the longest and highest-resistance branch governs. Always size the fan for the critical path.
Conclusion
AHU selection is a four-step process: calculate supply airflow from cooling load and temperature difference, size the cooling coil for total heat removal and appropriate face velocity, calculate chilled water flow based on coil capacity and temperature differential, and finally size the supply fan for the system's total static pressure. Getting all four correct ensures your AHU performs reliably and efficiently throughout the building's lifecycle.
Speed up your AHU selection with the MEPMate AHU Sizing Calculator. Also use the Psychrometric Calculator to accurately determine mixed air and supply air enthalpies for precise coil duty calculations.