ℹ️ About This Calculator
A chiller is the heart of a central HVAC system — it produces chilled water that is distributed to AHUs and fan coil units throughout the building. Selecting the correct chiller tonnage is critical: undersizing means the building cannot be cooled; oversizing means the chiller cycles on and off, reducing efficiency and increasing maintenance costs. 1 TR (ton of refrigeration) = 3.517 kW of cooling.
AHRI Standard 550/590 governs chiller rating conditions. Air-cooled chillers are rated at 35°C ambient; water-cooled at 29°C entering condenser water. IPLV (Integrated Part Load Value) is the weighted average efficiency over a full operating season — more important than full-load efficiency for Indian buildings where the chiller runs at part load for most of the year. BEE (Bureau of Energy Efficiency) star ratings for chillers are based on IPLV.
📐 Chiller Sizing Formula
ASHRAE / AHRI
Cooling Capacity:
TR = Total Cooling Load (kW) / 3.517
or
TR = Total Cooling Load (BTU/hr) / 12,000
Chiller kW Input:
kW_input = TR × 3.517 / COP
Typical COP: Air-cooled: 2.8–3.5 | Water-cooled: 4.5–6.5
Chilled Water Flow:
Q_chw (L/s) = Cooling (kW) / (ρ × Cp × ΔT)
= kW / (4.187 × 5) [for 7/12°C CHW system]
Condenser Water Flow (water-cooled):
Q_cw = (Cooling kW + Compressor kW) / (4.187 × 5) [for 29/34°C CW]
❓ Frequently Asked Questions
🔗 Related Calculators
🧮 99 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators — IS/NBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →